Power consumption
< 1.1 VA/ 24 V DC ; < 2.2 VA/ 24 V AC
Temperature-measuring range
multi-range switching (see table) -35…+35°C; -35…+75°C; 0…+50°C; 0…+80°C
Operating range, humidity
0...95 % r. H. (without dew formation)
Voltage supply
24 V AC (± 20 %) and
15…36 V DC
Deviation of humidity
typical ± 2.0 % r. H. (20…80 % r. H. ); at + 25 °C, otherwise ± 3.0 % r. H.
Load resistance
RL > 5 kOhm
Measuring range, humidity
0...100 % r. H.
(output corresponding to 0 -10 V)
Output, humidity
0 - 10 V
Measuring range, temperature
multi-range switching
with 4 switchable measuring ranges
–35...+35 °C; –35...+75 °C; 0...+50 °C; 0...+80 °C
(output corresponding to 0 -10 V or 4...20 mA)
Ambient temperature
storage –5...+60 °C
operation –5...+60 °C
Electrical connection
2-, 3- or 4-wire connection
0.14 -1.5 mm ² via terminal screws on circuit board
Temperature deviation
typically ± 0.2 K at +25 °C
Cable connection
cable gland, plastic (M 16 x 1.5; with strain relief, exchangeable, max. inner diameter 10.4 mm) or
M12 connector according to DIN EN 61076-2-101 (optional on request)
Cable gland
M 16 x 1.5, including strain relief, exchangeable,
max. inner diameter 10.4 mm
Connecting head
made of plastic, material polycarbonate (PC), colour white,
pluggable, Ø = approx. 35 mm, H = approx. 29 mm,
with metal sinter filter made of stainless steel V4A (1.4404)
sensor cable
PVC, LiYY, 4 x 0.14 mm²,
KL = approx. 2 m