Power consumption
< 1.1 VA/ 24 V DC ; < 2.2 VA/ 24 V AC
Temperature-measuring range
multi-range switching (see table) -35…+35°C; -35…+75°C; 0…+50°C; 0…+80°C
Operating range, humidity
0...95 % r. H. (without dew formation)
Voltage supply
15...36 V DC
depending on working resistance, residual ripple stabilised ± 0.3 V
Deviation of humidity
typical ± 2 % r. H. (20…80 % r. H. ); at + 25 °C, otherwise ± 3 %
Working resistance
Ra (ohm) = (Ub -14 V)/ 0.02 A for I variant
Measuring range, humidity
0...100 % r. H.
(output corresponding to 4...20 mA)
Output, humidity
4...20 mA
Measuring range, temperature
multi-range switching
with 4 switchable measuring ranges
–35...+35 °C; –35...+75 °C; 0...+50 °C; 0...+80 °C
(output corresponding to 0 -10 V or 4...20 mA)
Operating range, temperature
–35...+80 °C
Sensor protection
plastic sinter filter, Ø 16 mm, L = 35 mm, exchangeable
(optional metal sinter filter, Ø 16 mm, L = 32 mm)
Ambient temperature
storage –5...+60 °C
operation –5...+60 °C
Protective tube
stainless steelV2A (1.4301), Ø = 16 mm, L = 142 mm
Electrical connection
2-, 3- or 4-wire connection
0.14 -1.5 mm ² via terminal screws on circuit board
Temperature deviation
typically ± 0.2 K at +25 °C
Output, temperature
4...20 mA
Cable connection
cable gland, plastic (M 16 x 1.5; with strain relief, exchangeable, max. inner diameter 10.4 mm) or
M12 connector according to DIN EN 61076-2-101 (optional on request)
Cable gland
M 16 x 1.5, including strain relief, exchangeable,
max. inner diameter 10.4 mm
sensor cable
PVC, LiYY, 6 x 0.14 mm²,
KL = approx. 2 m (other lengths optional)