The sensor device is installed on cooling ceilings, cooling or cold-water pipes and cooled surfaces, and has been designed to prevent the formation of condensation. It reliably detects the formation of dew by means of its humidity and temperature sensor (no conductivity measurement). Thanks to its measuring method of pro-dynamic cross-convection it yields precise measuring results (with LED status indicator). Dew point temperature is the temperature at which the air reaches the state of saturation and water vapour starts to condensate. 

Protection type
Output model
Housing version
HYGRASGARD®
Quantity

Voltage supply

24 V AC (± 20 %) and

15…36 V DC

Switchpoint

approx. 93 % r.H. (permanently set)

Power consumption

< 1.1 VA/ 24 V DC ; < 2.2 VA/ 24 V AC

Output

potential-free changeover contact (24 V), 1 A ohmic load

Output signal

potential-free changeover contact (24 V), 1 A ohmic load

Sensor protection

membrane filter

Medium

clean air and

non-aggressive, non-combustible gases

Process connection

endless metal strap with metal tightener,

300 mm, for pipes up to 3 ''

(included in scope of delivery)

Electrical connection

0.14 - 1.5 mm² via terminal screws

Cable connection

cable gland, plastic (M 16 x 1.5; with strain relief, exchangeable, max. inner diameter 10.4 mm) or

M12 connector according to DIN EN 61076-2-101 (optional on request)

Housing

plastic, UV-stabilised,

material polyamide, 30 % glass-globe reinforced,

with quick-locking screws

(slotted/ Phillips head - combination),

colour traffic white (similar to RAL 9016)

Housing dimensions

72 x 64 x 43.3 mm (Tyr 1 with Display)

Cable gland

M 16 x 1.5, including strain relief, exchangeable,

max. inner diameter 10.4 mm

Installation

The mounting position should be selected

so that no condensate can enter the sensor system

in the event that condensation forms!

KW

with strap for direct mounting on pipes or

for direct mounting on flat surfaces (e.g. walls, ceilings)

KW - external

with detached sensor head

(cable length KL = 1.5 m) for mounting on pipes

Protection class

III (according to EN 60 730)

Protection type

IP 65

1202-1025-0001-040