Voltage supply
24 V AC (± 20 %) and
15…36 V DC
Switchpoint
approx. 93 % r.H. (permanently set)
Power consumption
< 1.1 VA/ 24 V DC ; < 2.2 VA/ 24 V AC
Output
potential-free changeover contact (24 V), 1 A ohmic load
Output signal
potential-free changeover contact (24 V), 1 A ohmic load
Sensor protection
membrane filter
Medium
clean air and
non-aggressive, non-combustible gases
Process connection
endless metal strap with metal tightener,
300 mm, for pipes up to 3 ''
(included in scope of delivery)
Electrical connection
0.14 - 1.5 mm² via terminal screws
Cable connection
cable gland, plastic (M 16 x 1.5; with strain relief, exchangeable, max. inner diameter 10.4 mm) or
M12 connector according to DIN EN 61076-2-101 (optional on request)
Housing
plastic, UV-stabilised,
material polyamide, 30 % glass-globe-reinforced
colour traffic white (similar to RAL 9016)
ALTF 02 with snap-on lid,
Housing dimensions
72 x 64 x 37.8 mm (Tyr 01)
Cable gland
M 16 x 1.5, including strain relief, exchangeable,
max. inner diameter 10.4 mm
Installation
The mounting position should be selected
so that no condensate can enter the sensor system
in the event that condensation forms!
KW - SD
with strap for direct mounting on pipes or
for direct mounting on flat surfaces (e.g. walls, ceilings)
KW - SD - external
with detached sensor head
(cable length KL = 1.5 m) for mounting on pipes
Protection class
III (according to EN 60 730)
Protection type
IP 43