Room CO2 and temperature sensor or measuring transducer AERASGARD® FSCO2/FSTM-CO2

€362.03
Tax included

The AERASGARD® FSCO2 / FSTM - CO2 room climate transmitter with in-wall housing is used for measuring The CO2 content and temperature of the air. It converts the measured values into a standard signal of 0-10 V.

The CO2 content of the air is measured using an optical NDIR sensor (non-dispersive infra-red technology). A digital, long-term stable sensor is used for temperature measurement.

Measured variables
AERASGARD, RHEASGARD & RHEASREG
Quantity

Voltage supply

24 V AC/ DC (± 10 %)

Power consumption

< 1.5 VA/ 24 V DC, < 2.8 VA/ 24 V AC

Measuring range, CO2

Sensor, CO2

optical NDIR sensor

(non-dispersive infra-red technology),

with manual calibration (via zero button) and

automatic calibration (fixed)

Output, CO2

0 - 10 V

Measuring accuracy, CO2

typically ± 30 ppm ± 3 % of measured value

Temperature dependence, CO2

± 5 ppm/ °C or ± 0.5 % of measured value/ °C

(whichever is higher)

Pressure dependence

± 0,13 %/ mm Hg

Gas exchange

by diffusion

Warm up time

approx. 1 hour

Response time

< 2 minutes

Ambient temperature

storage –35...+85 °C;

operation 0...+50 °C

Medium

clean air and

non-aggressive, non-combustible gases

Electrical connection

0.14 - 1.5 mm², using plug terminals

Housing

plastic, colour pure white glossy (similar to RAL 9010)

(other colours are possible on request with colour variants

depending on the respective switch programme)

Installation

in in-wall flush box Ø 55 mm

Long-term stability

< 2 % in 15 years

Permissible air humidity

max. 90 % r. H., non-precipitating air

Protection class

III (according to EN 60 730)

Protection type

IP 20 

1501-9120-1001-162