AERASGARD® RFTM-LQ-CO2-W

€441.10
Tax included

Maintenance-free room sensor AERASGARD® RTM - CO2 - SD with active output, automatic calibration (fixed), in an elegant plastic housing with snap-on cover, for determining the CO2 content of the air (0...2000 ppm) and the temperature (0...+50°C). The measuring transducer converts the measured values into a standard signal of 0-10 V.

The sensor device is used in offices, hotels, convention centres, apartments, shops, etc. for the purpose of evaluating the indoor climate. This enables energy-saving room ventilation on an as-needed basis, thereby reducing operating costs and improving well-being.

Output
Display
Measured variables
AERASGARD, RHEASGARD & RHEASREG
Quantity

Voltage supply

24 V AC/ DC (± 10 %)

Power consumption

< 4.4 W/ 24 V DC typical; < 6.4 VA/ 24 V AC typical;

peak current 200 mA

Measuring range, humidity

0...100 % r. H.

Operating range, humidity

0...95 % r. H. (without dew formation)

Deviation of humidity

typical ± 2 % r. H. (20…80 % r. H. ); at + 25 °C, otherwise ± 3 %

Output, humidity

0 -10 V or 4...20 mA (selectable via DIP switches)

Measuring range, temperature

0...+ 50 °C (output equivalent to 0 -10 V or 4...20 mA)

Operating range, temperature

0...+50 °C

Temperature deviation

typically ± 0.2 K at +25 °C

Output, temperature

0 -10 V or 4...20 mA (selectable via DIP switches)

Sensor, VOC

VOC sensor (metal oxide) (VOC = volatile organic compounds),

with manual calibration (via zero button),

with automatic calibration (can be deactivated via DIP switches)

Measuring range, VOC

0...100 % air quality; referred to calibrating gas;

multi-range switching (selectable via DIP switches)

VOC sensitivity low, medium, high

Output, VOC

0 -10 V (0 V = clean air, 10 V = polluted air) or 4...20 mA (selectable via DIP switches,

switchpoint can be adjusted from 0...100 % of the output signal)

Measuring accuracy, VOC

± 20 % of final value (referred to calibrating gas)

Service life

> 60 months (under normal load conditions)

depending on the type of loading and gas concentration

Measuring range, CO2

0...2000 ppm or 0...5000 ppm (selectable via DIP switches)

Sensor, CO2

Optical NDIR sensor (non-dispersive infra-red technology),

with manual calibration (via zero button),

with automatic calibration (can be deactivated via DIP switches)

Output, CO2

0 -10 V or 4...20 mA (selectable via DIP switches)

Measuring accuracy, CO2

typically ± 30 ppm ± 3 % of measured value

Temperature dependence, CO2

± 5 ppm/ °C or ± 0.5 % of measured value/ °C

(whichever is higher)

Pressure dependence

± 0,13 %/ mm Hg

Gas exchange

by diffusion

Relay output

with potential-free changeover contact (24 V / 1 A)

(assignment selectable via DIP switches, switchpoint adjustable)

Warm up time

approx. 1 hour

Response time

< 2 minutes

Output

0 -10 V or 4...20 mA (selectable via DIP switches,

selected variant applies for all outputs), working resistance < 800 Ω

Output

0 -10 V or 4...20 mA, working resistance < 800 Ω

(selectable via DIP switches, selected variant applies for all outputs),

with offset potentiometer (± 10 % of the measuring range)

Ambient temperature

0...+50 °C

Electrical connection

0.14 - 1.5 mm² via terminal screws

Housing

plastic, material ABS,

colour pure white (similar to RAL 9010)

Dimensions

98 x 98 x 33 mm (Baldur 2)

Installation

wall mounting or on in-wall flush box, Ø 55 mm,

base with 4 holes, for attachment to vertically or

horizontally installed in-wall flush boxes for rear cable entry,

with predetermined breaking point for cable entry

from top/ bottom in case of plain on-wall installation

Long-term stability

< 2 % in 15 years

Protection class

III (according to EN 60 730)

Protection type

IP 30

1501-61B8-7301-500