Voltage supply
24 V AC/ DC (± 10 %)
Power consumption
< 1.5 VA/ 24 V DC, < 2.8 VA/ 24 V AC
Measuring range, temperature
0...+50 °C
Temperature deviation
typically ± 0.8 K at +25 °C
Output, temperature
0 - 10 V
Measuring range, CO2
Sensor, CO2
optical NDIR sensor
(non-dispersive infra-red technology),
with manual calibration (via zero button) and
automatic calibration (fixed)
Output, CO2
0 - 10 V
Measuring accuracy, CO2
typically ± 30 ppm ± 3 % of measured value
Temperature dependence, CO2
± 5 ppm/ °C or ± 0.5 % of measured value/ °C
(whichever is higher)
Pressure dependence
± 0,13 %/ mm Hg
Gas exchange
by diffusion
Warm up time
approx. 1 hour
Response time
< 2 minutes
Sensor
digital temperature sensor,
low hysteresis, high long-term stability
Ambient temperature
storage –35...+85 °C;
operation 0...+50 °C
Medium
clean air and
non-aggressive, non-combustible gases
Electrical connection
0.14 - 1.5 mm², using plug terminals
Housing
plastic, colour pure white glossy (similar to RAL 9010)
(other colours are possible on request with colour variants
depending on the respective switch programme)
Installation
in in-wall flush box Ø 55 mm
Long-term stability
< 2 % in 15 years
± 1 %/ year
Permissible air humidity
max. 90 % r. H., non-precipitating air
Protection class
III (according to EN 60 730)
Protection type
IP 20