Power consumption
< 2 VA/ 24 V DC, < 3.5 VA/ 24 V AC
Voltage supply
24 V AC (± 20 %) and
15…36 V DC
Load resistance
RL > 5 kOhm
Connection type
2- or 3-wire connection
Measuring ranges
multi-range switching with 8 switchable measuring ranges
Media temperature
–20...+50 °C
Pressure connection
4/ 6 x 11 mm (hoses Ø = 4/ 6 mm),
metal pressure connection nozzles
Type of pressure
differential pressure
Zero point offset
< ± 0.7 % of final value
± 1.4 % of final value for pressure ranges < 250 Pa
Above- below-pressure
máx. ± 100 hPa
Medium
clean air and
non-aggressive, non-combustible gases
Signal filtering
switchable 1 s/ 10 s
Electrical connection
2- or 3-wire connection
0.14 - 1.5 mm², via plug-in screw terminal
Housing dimensions
126 x 90 x 50 mm (Tyr 2)
Cable gland
M 16 x 1.5; including strain relief
Dimensions
126 x 90 x 50 mm (Tyr 2)
Output
0 - 10 V
Sum of Linearity+hysteresis
< ± 1 % of final value
± 2 % of final value for pressure ranges < ± 250 Pa
Output signal
0 - 10 V
Temperature drift values
± 0.1 % / °C
± 0.3 % / °C for pressure ranges < 250 Pa
Air humidity
< 95 % r. H., non-precipitating air
Protection class
III (according to EN 60 730)
Protection type
IP 65 (according to EN 60 529)*
Accuracy
(100 Pa): typically ± 2 Pa
compared to the calibrated reference device
Measuring range pressure
0 ... +50 Pa / -50 ... +50 Pa
0 ... +100 Pa / -100 ... +100 Pa
Cable connection
Cable fitting, plastic
(M 16 x 1.5; with strain relief, exchangeable,
max. inner diameter 10.4 mm)