The sensor device has a housing made of impact resistant plastic, with cable gland or M12 connector according to DIN EN 61076-2-101 and with metal pressure port nozzles (quick connect optional). It is used to measure positive, negative or differential pressures in clean air, with limit value switching. The piezoresistive measuring element guarantees a high degree of reliability and accuracy.
Voltage supply
24 V AC/ DC (± 20 %)
Power consumption
< 1,0 VA/ 24 V DC
< 2,2 VA/ 24 V AC
Load resistance
RL > 5 kOhm
Output
0 -10 V
1 changeover contact (24 V), 1 A ohmic load
Output signal
0 -10 V
1 changeover contact (24 V), 1 A ohmic load
Connection type
3-wire connection
Measuring range
multi-range switching with 8 switchable measuring ranges
Media temperature
–20...+50 °C
Pressure connection
4/ 6 x 11 mm (hoses Ø = 4/ 6 mm),
metal pressure connection nozzles
Type of pressure
differential pressure
Zero point offset
< ± 0.7 % of final value
Above- below-pressure
máx. ± 100 hPa
Medium
clean air and
non-aggressive, non-combustible gases
Signal filtering
switchable 1 s/ 10 s
Setting increment p
1 % of pressure range (100 Pa => 1 Pa; 5000 Pa => 50 Pa)
Measuring ranges
0... 100 Pa/ – 100... + 100 Pa
0... 300 Pa/ – 300... + 300 Pa
0... 500 Pa/ – 500... + 500 Pa
0... 1000 Pa/ – 1000... + 1000 Pa
Switching hysteresis
± 1 % of pressure range (100 Pa => ± 1 Pa; 5000 Pa => ± 50 Pa)
Electrical connection
3-wire connection (U)
0.14 - 1.5 mm², via plug-in screw terminal
Housing dimensions
126 x 90 x 50 mm (Tyr 2)
Accuracy
(1000 Pa): typically ± 5 Pa
compared to the calibrated reference device
Cable gland
M 16 x 1.5; including strain relief
Dimensions
126 x 90 x 50 mm (Tyr 2)
Sum of Linearity+hysteresis
< ± 1 % of final value
Measuring range pressure
0... 100 Pa/ – 100... + 100 Pa
0... 300 Pa/ – 300... + 300 Pa
0... 500 Pa/ – 500... + 500 Pa
0... 1000 Pa/ – 1000... + 1000 Pa
Temperature drift values
± 0.1 %/ °C
Air humidity
< 95 % r. H., non-precipitating air
Protection class
III (according to EN 60 730)
Protection type