Volume flow meter PREMASREG® 716x

€264.90
Tax included

The electronic PREMASREG® 716x pressure sensor and switch features measuring functions for volume flow, differential pressure, filter monitoring and liquid level detection based on pressure measurement in clean air. The device has a housing made of impact resistant plastic, with cable gland or M12 connector according to DIN EN 61076-2-101, and with metal pressure port nozzles (quick connect optional). It provides one switching output, one continuous output and a back-lit display for setting the switching point and showing actual values. The piezoresistive measuring element guarantees a high degree of reliability and accuracy.

Output model
Pressure range
PREMASGARD® / PREMASREG®
Quantity

Voltage supply

24 V AC/ DC (± 10 %) and 15...36 V DC

Power consumption

< 1.5 VA/ 24 V DC, < 2.8 VA/ 24 V AC

Load resistance

RL > 5 kOhm

Output

0 -10 V

1 changeover contact (24 V), 1 A ohmic load

Output signal

0 -10 V

1 changeover contact (24 V), 1 A ohmic load

Connection type

3-wire connection

Measuring function

Volume flow, differential pressure,

filter monitoring, fill level (adjustable)

Measuring ranges

10...100% (adjustable)

Media temperature

–20...+50 °C

Pressure connection

4/ 6 x 11 mm (hoses Ø = 4/ 6 mm),

metal pressure connection nozzles

Type of pressure

differential pressure

Above- below-pressure

máx. ± 10000 Pa

Medium

clean air and

non-aggressive, non-combustible gases

Signal filtering

switchable 1 s/ 10 s

and small value suppression < 1 %

Signal hysteresis

± 1 % or final value (pressure) 10 Pa/ 50 Pa

Electrical connection

3-wire connection

0.14 - 1.5 mm², via plug-in screw terminal

Housing dimensions

126 x 90 x 50 mm (Tyr 2)

Cable gland

M 20 x 1.5; including strain relief

Dimensions

126 x 90 x 50 mm (Tyr 2)

Accuracy

(1000 Pa): typically ± 5 Pa

compared to the calibrated reference device

Sum of Linearity+hysteresis

< ± 1 % of final value

Temperature drift values

± 0.1 %/ °C

Measuring range pressure

0 ... 1000 Pa,

volume flow: 10...100% [m3/s][m3/min] [m3/h] [l/s] [l/min] [l/h]

filter monitoring: 10...100%

liquid level detection: 0 - 8 ... 14cm

Air humidity

< 95 % r. H., non-precipitating air

Protection class

III (according to EN 60 730)

Protection type

IP 65 (according to EN 60 529)*

Standards

CE conformity,

according to EMC directive 2014/ 30/ EU,

according to EN 61326-1, according to EN 61326-2-3

Features

Display with illumination, three-line,

cutout approx. 70 x 40 mm (W x H),

for displaying the volume flow, differential pressure,

contamination degree or level

and for setting the switchpoint, K factor, measuring range limits

and other settings

Cable connection

Cable fitting, plastic

(M 16 x 1.5; with strain relief, exchangeable,

max. inner diameter 10.4 mm)

K factor

1 to 3000 (adjustable)

Housing

plastic, UV-stabilised,

material polyamide, 30 % glass-globe reinforced,

with quick-locking screws

(slotted/ Phillips head - combination),

colour traffic white (similar to RAL 9016),

housing cover for display is transparent !

1302-7161-4161-200