Voltage supply
24 V AC/ DC (± 10 %)
Power consumption
< 1 W at 24 V DC; < 2 VA at 24 V AC
Working resistance
Ra (Ohm) = 25 ...450 Ohm for I variant
Load resistance
RL > 25 kOhm for U variant
Max. pressure
± 0.5 % of final value per year
Output
switchable 0 -10 V/ 4...20 mA (via DIP switches)
Connection type
3-wire connection
Current consumption
max. 20 mA (at 24 V DC)
Measuring ranges
multi-range switching with 4 switchable measuring ranges
Type of pressure
atmospheric pressure/ absolute pressure
Accuracy
typically ± 1.5 % of final value (at +20°C)
Zero point offset
± 50 hPa
Above- below-pressure
200 kPa
Ambient temperature
–10...+50 °C
Storage temperature
–20...+50 °C
Medium
clean air and
non-aggressive, non-combustible gases
Signal filtering
0 s/ 1 s/ 5 s/ 10 s (selectable via DIP switches)
Electrical connection
2- or 3-wire connection
0.14 - 1.5 mm² via terminal screws
Cable connection
cable gland, plastic (M 16 x 1.5; with strain relief,
exchangeable, max. inner diameter 10.4 mm) or
M12 connector (male, 5-pin, A-code)
according to DIN EN 61076-2-101 (optional on request)
Cable gland
M 16 x 1.5, including strain relief, exchangeable,
max. inner diameter 10.4 mm
Long-term stability
± 0.5 % of final value per year
Hysteresis
± 0.1 % of final value
Temperature drift values
± 0.1 % of final value/ °C
Temperature drift values
± 0.5 % of final value per 10 K
Linearity
± 0.5 % of final value
Air humidity
< 95 % r. H., non-precipitating air
Housing
plastic, UV-stabilised,
material polyamide, 30 % glass-globe reinforced,
with quick-locking screws
(slotted/ Phillips head - combination),
colour traffic white (similar to RAL 9016)
Protection class
III (according to EN 60 730)
Housing dimensions
72 x 64 x 37,8 mm (Tyr 1)
Protection type
IP 65