Power consumption
< 1,0 VA/ 24 V DC
< 2,2 VA/ 24 V AC
Voltage supply
15...36 V DC
depending on working resistance, residual ripple stabilised ± 0.3 V
Working resistance
Ra (ohm) = (Ub -14 V)/ 0.02 A for I variant
Temperature deviation
typically ± 0.2 K at +25 °C
Output
4...20 mA
Sensor
Pt1000, DIN EN 60751, class B
(Perfect Sensor Protection)
Connection type
2- or 3-wire connection
Ambient temperature
Measuring transducer –30...+70 °C
Insulating resistance
100 MΩ,
at +20 °C (500V DC)
Electrical connection
0.14 - 1.5 mm² via terminal screws
Housing dimensions
143 x 97 x 61 mm (Tyr 2E)
Permissible air humidity
< 95 % r. H., non-precipitating air
Protection class
III (according to EN 60 730)
Sensor protection
sensor sleeve, stainless steel V4A (1.4571), Ø = 6 mm,
nominal length NL = 50 mm (other dimensions optionally available)
cable entry stamped (optionally rolled)
Protection type housing
IP 65 (according to EN 60 529)
Housing tested, TÜV SÜD, Report No. 713160960B (Skadi2)
Measuring ranges
multi-range switching with 8 switchable measuring ranges,
see table (other ranges optional)
with manual zero point correction (± 10 K)
Cable connection
M12 connector
(male, 5-pin, A-code)
according to DIN EN 61076-2-101
Housing
stainless steel V4A (1.4571),
with non-distortion cover bolting,
impact-resistant, high EMI shielding,
corrosion, temperature, UV and weathering resistant
sensor cable
silicone, SiHF, 2 x 0.25 mm², KL = 1.5 m (other lengths and
range limits optional, e.g. PTFE leads up to +250 °C
or glass fibre with steel wire mesh up to +350°C)
Protection type (sensor)
IP 65