Power consumption
< 1.0 VA/ 24 V AC/ DC; < 0.55 VA/ 24 V DC
Voltage supply
15...36 V DC
depending on working resistance, residual ripple stabilised ± 0.3 V
Working resistance
máx. 750 Ohm/ 24 V DC
Temperature deviation
typically ± 0.2 K at +25 °C
Sensor
Pt1000, DIN EN 60751, class B,
glass sensing resistor
(Perfect Sensor Protection)
Connection type
2- or 3-wire connection
Measuring ranges
multi-range switching with 8 switchable measuring ranges,
see table (other ranges optional)
with manual zero point correction (± 10 K)
Ambient temperature
Measuring transducer –30...+70 °C
Process connection
screwed socket with G ½ " straight pipe thread
Protective tube
stainless steel, 1.4571, V4A,
G ½ " straight pipe thread, wrench size 27 mm,
pmax = 40 bar, Ø = 8 mm
length of neck tube (HL) = 80 mm
inserted length (EL) = 100 - 400 mm
Electrical connection
0.2 - 1.5 mm², via push-in terminal
Connecting head
form B, material aluminium,
colour white aluminium (similar to RAL 9006),
M 20 x 1.5
Permissible air humidity
< 95 % r. H., non-precipitating air
Output
4...20 mA
Protection class
III