Power consumption
< 1,0 VA/ 24 V DC
< 2,2 VA/ 24 V AC
Voltage supply
24 V AC/ DC (± 10 %)
Temperature deviation
typically ± 0.2 K at +25 °C
Load resistance
RL > 5 kOhm
Sensor
Pt1000, DIN EN 60751, class B
Connection type
2- or 3-wire connection
Ambient temperature
measuring transducer –5...+60 °C
Connection cable
PVC; LiYY, 1.5 m
(other lengths optional: e.g. 3 m, 6 m)
Electrical connection
0.14 - 1.5 mm² via terminal screws
Cable gland
M 16 x 1.5, including strain relief, exchangeable,
max. inner diameter 10.4 mm
sensor cable
PVC, H03VV-F, 2 x 0.5 mm²,
KL = approx. 1.5 m (other lengths optional)
Humidity
< 95 % r. H., non-precipitating air
Protection class
III (according to EN 60 730)
Protection type
IP 65 (according to EN 60 529)*
Output
0 - 10 V
Measuring ranges
multi-range switching with 8 switchable measuring ranges
(other ranges optional) Tmin –5 °C, Tmax +60 °C
with manual zero point correction (± 10 K)
Globe
plastic, colour black, Ø = 50 mm
Cable connection
cable gland, plastic (M 16 x 1.5; with strain relief, exchangeable, max. inner diameter 10.4 mm) or
M12 connector according to DIN EN 61076-2-101 (optional on request)
Housing
plastic, UV-stabilised,
material polyamide, 30 % glass-globe reinforced,
with quick-locking screws
(slotted/ Phillips head - combination),
colour traffic white (similar to RAL 9016),
housing cover for display is transparent !
Housing dimensions
72 x 64 x 43.3 mm (Tyr 1 with Display)
Standards
CE conformity,
electromagnetic compatibility according to EN 61326,
according to EMC Directive 2014/ 30/ EU
Display
display with illumination, two-line, cut-out approx. 36 x15 mm (B x H),
to display the actual temperature and internal diagnostics
(measuring range exceeded, measuring range not reached,
sensor breakage, sensor short circuit)