Pressure and differential pressure measuring transducer PREMASGARD 7110-I Q

€271.66
Tax included

The calibratable pressure transmitters of the PREMASGARD® 711x series with eight switchable measuring ranges (eight devices in one), housing made of impact resistant plastic, optionally with/without display, with cable gland or M12 connector according to DIN EN 61076-2-101 and with metal pressure port nozzles (quick connect optional) serve to measure positive, negative or differential pressures in air. The piezoresistive measuring element is temperature-compensated and guarantees a high degree of reliability and accuracy.

Output
Display
Pressure range
PREMASGARD® / PREMASREG®
Cable connection
Quantity

Power consumption

< 2 VA/ 24 V DC, < 3.5 VA/ 24 V AC

Voltage supply

15...36 V DC

depending on working resistance, residual ripple stabilised ± 0.3 V

Working resistance

Ra (ohm) = (Ub -14 V)/ 0.02 A for I variant

Connection type

2- or 3-wire connection

Measuring ranges

multi-range switching with 8 switchable measuring ranges

Media temperature

–20...+50 °C

Pressure connection

4/ 6 x 11 mm (hoses Ø = 4/ 6 mm),

metal pressure connection nozzles

Type of pressure

differential pressure

Zero point offset

< ± 0.7 % of final value

± 1.4 % of final value for pressure ranges < 250 Pa

Above- below-pressure

máx. ± 100 hPa

Medium

clean air and

non-aggressive, non-combustible gases

Signal filtering

switchable 1 s/ 10 s

Electrical connection

2- or 3-wire connection

0.14 - 1.5 mm², via plug-in screw terminal

Housing dimensions

126 x 90 x 50 mm (Tyr 2)

Output

4...20 mA

Cable gland

M 16 x 1.5; including strain relief

Dimensions

126 x 90 x 50 mm (Tyr 2)

Sum of Linearity+hysteresis

< ± 1 % of final value

± 2 % of final value for pressure ranges < ± 250 Pa

Temperature drift values

± 0.1 % / °C

± 0.3 % / °C for pressure ranges < 250 Pa

Air humidity

< 95 % r. H., non-precipitating air

Protection class

III (according to EN 60 730)

Protection type

IP 65 (according to EN 60 529)*

Accuracy

(100 Pa): typically ± 2 Pa

compared to the calibrated reference device

Measuring range pressure

0... +50 Pa/ –50... +50 Pa

0...+100 Pa/ –100...+100 Pa

Cable connection

M12 connector

(male, 5-pin, A-code)

2004-6131-2100-021