Pressure, differential pressure and volume flow measuring transducers PREMASGARD® 112x

€144.87
Tax included

The calibratable, compact pressure sensors PREMASGARD® 112x (series) are equipped with eight switchable measuring ranges and with or without optional display (eight devices in one) and are used for measuring above-atmospheric, below-atmospheric, or differential pressures and volume flow in air. The piezoresistive measuring element is temperature-compensated and guarantees a high degree of reliability and accuracy.

The pressure transmitters feature a configurable offset and a button for manual zero adjustment. Applications of these sensor devices are found in cleanroom, medical and filter engineering, in ventilation and air conditioning ducts, in spray booths and large-scale catering facilities, in filter monitoring and level measuring or frequency converter triggering.

Output
Display
Pressure range
PREMASGARD® / PREMASREG®
Quantity

Power consumption

< 1 W at 24 V DC; < 2 VA at 24 V AC

Voltage supply

15...36 V DC

depending on working resistance, residual ripple stabilised ± 0.3 V

Measuring function

Differential pressure, volume flow (square root output signal)

Current consumption

< 20 mA

Measuring ranges

multi-range switching with 8 switchable measuring ranges

Media temperature

–20...+50 °C

Pressure connection

with connection nozzles for pressure hose Ø 6 mm

Type of pressure

differential pressure

Zero point offset

± 5 % of final value

Above- below-pressure

max. 5 x pressure range

Medium

clean air and

non-aggressive, non-combustible gases

Output

4...20 mA

Signal filtering

switchable 1 s/ 10 s

Electrical connection

2- or 3-wire connection

0.14 - 1.5 mm² via terminal screws

Cable connection

cable gland, plastic (M 16 x 1.5; with strain relief, exchangeable, max. inner diameter 10.4 mm) or

M12 connector according to DIN EN 61076-2-101 (optional on request)

Cable gland

M 16 x 1.5, including strain relief, exchangeable,

max. inner diameter 10.4 mm

Long-term stability

± 1 %/ year

Hysteresis

0.3 % of final value

Media contacting parts

ms, Ni, Nylon, PU, Si, PVC with plasticisers

Temperature drift values

± 0.1 % of final value/ °C

Accuracy

(1000 Pa): ± typically 10 Pa

compared to the calibrated reference device

Linearity

< ± 1 % of final value

Air humidity

< 95 % r. H., non-precipitating air

Protection class

III (according to EN 60 730)

Measuring range pressure

0 ... +100 Pa / -100 ... +100 Pa

0 ... +300 Pa / -300 ... +300 Pa

0 ... +500 Pa / -500 ... +500 Pa

0 ... +1000 Pa / -1000 ... +1000 Pa

Protection type

IP 67

1301-1172-0010-000