![](https://acsinstal.eu/1161-large_default/pressure-measuring-transducer-premasgard-shdshd-sd.jpg)
![](https://acsinstal.eu/1161-large_default/pressure-measuring-transducer-premasgard-shdshd-sd.jpg)
The PREMASGARD® SHD ressure transmitter measures relative pressures in the bar range. It converts the measurand into a standard signal of 0-10 V or 4...20 mA. Process connection is G ½" straight external pipe thread. The SHD device is used for pressure measuring in gaseous and liquid media. Applications can be found in hydraulics and pneumatics, in process, mechanical and plant engineering. The pressure measuring cell is gasketless welded together with the pressure transducer.
Voltage supply
24 V AC/ DC for output 0 -10 V
7 - 33 V DC for output 4 ... 20 mA
Response time
2 ms (1 ms typical)
Characteristic line
± 0,3 %
Output
4...20 mA
Output signal
4... 20 mA, 2-wire, (working resistance < (UB (V) -7 V)/ 0,02 A ;
RL depending on working resistance
Measuring range
0...2,5 bar
Measuring principle
steel measuring cell
Media temperature
– 40...+135 °C
Pressure connection
G ½ " sealing at the back, and manometer (combined)
with profile gasket FPM, special WW G ¼ " DIN 3852
Type of pressure
relative
Measuring range pressure
0...2,5bar
Overload range
< 6 bar: 5 x of final value
> 6 bar: 3 x of final value (max. 1500 bar)
Bursting pressure
< 6 bar: 10 x of final value
> 6 bar: 6 x of final value (max. 2500 bar)
Electrical connection
0.25 - 1.5 mm², via plug-in connector DIN EN 175301-803-A
Housing
stainless steel 1.4305
Connecting head
plastic, approx. 98 x 50 x 34 mm
Installation
directly on pressure line
Medium contacting parts
stainless steel 1.4305
Protection class
III (according to EN 60 730)
Protection type
IP 65