Pressure measuring transducers/ switches/ monitors for volume flow PREMASREG 7161-U VAQ LCD

€765.43
Tax included

The electronic PREMASREG® 761x - VA pressure sensor and switch is equipped with measuring functions for volume flow, differential pressure, filter monitoring and liquid level detection based on pressure measurement in clean air. The devices feature a V4A stainless steel housing, a cable gland or M12 connector according to DIN EN 61076-2-101 and a stainless steel quick-connect pressure port (pipe fitting optional). They provide one switching output, one continuous output and a back-lit display for setting the switching point and showing actual values. The piezoresistive measuring element guarantees a high degree of reliability and accuracy.

Output model
Pressure range
PREMASGARD® / PREMASREG®
Quantity

Voltage supply

24 V AC/ DC (± 10 %) and 15...36 V DC

Power consumption

< 1.5 VA/ 24 V DC, < 2.8 VA/ 24 V AC

Load resistance

RL > 5 kOhm

Output

0 -10 V

1 changeover contact (24 V), 1 A ohmic load

Output signal

0 -10 V

1 changeover contact (24 V), 1 A ohmic load

Connection type

3-wire connection

Measuring function

Volume flow, differential pressure,

filter monitoring, fill level (adjustable)

Measuring ranges

10...100% (adjustable)

Media temperature

–20...+50 °C

Type of pressure

differential pressure

Above- below-pressure

máx. ± 10000 Pa

Medium

clean air and

non-aggressive, non-combustible gases

Signal filtering

switchable 1 s/ 10 s

and small value suppression < 1 %

Signal hysteresis

± 1 % or final value (pressure) 10 Pa/ 50 Pa

Electrical connection

0.14 - 1.5 mm², via plug-in screw terminal

Pressure connection

equipped as standard with quick connect made from stainless steel

for PVC-fabric pressure hose Ø 6 mm ( 4/ 8 mm optional)

optionally with pipe fitting, stainless steel V2A (1.4305)

for pressure lines Ø 6 mm

Housing dimensions

143 x 97 x 61 mm (Tyr 2E)

Sum of Linearity+hysteresis

< ± 1 % of final value

Accuracy

(1000 Pa): typically ± 5 Pa

compared to the calibrated reference device

Temperature drift values

± 0.1 %/ °C

Air humidity

< 95 % r. H., non-precipitating air

Protection class

III (according to EN 60 730)

Cable connection

M12 connector (male, 12-pin, A-code)

according to DIN EN 61076-2-101

K factor

1 to 3000 (adjustable)

Housing

stainless steel V4A (1.4571),

with non-distortion cover bolting,

impact-resistant, high EMI shielding,

corrosion, temperature, UV and weathering resistant

2004-6192-4100-021

16 same category products: