Power consumption
< 1 W at 24 V DC; < 2 VA at 24 V AC
Voltage supply
15...36 V DC
depending on working resistance, residual ripple stabilised ± 0.3 V
Working resistance
Ra (ohm) = (Ub -14 V)/ 0.02 A for I variant
Deviation, humidity
typically < 5 % of final value
Sensor
light sensor
Ambient temperature
–30...+70 °C
Electrical connection
2-, or 3-wire connection
0.14 -1.5 mm ² via terminal screws on circuit board
Housing dimensions
72 x 64 x 37,8 mm (Tyr 1)
Output
4...20 mA
Cable gland
M 16 x 1.5, including strain relief, exchangeable,
max. inner diameter 10.4 mm
Measuring ranges
multi-range switching (via DIP switches)
with 6 switchable measuring ranges
0...500 Lux/ 1 kLux/ 2 kLux/ 5 kLux/ 20 kLux/ 60 kLux
(other individual ranges optional, e. g. 100 kLux)
sensor cable
PVC, LiYY, 4 x 0.14 mm²,
KL = approx. 2 m
Mounting (sensor)
inside suspended ceiling,
ceiling cutout Ø = 30 mm,
cover Ø = < 35 mm
Protection class
III (according to EN 60 730)
Cable connection
cable gland, plastic (M 16 x 1.5; with strain relief, exchangeable, max. inner diameter 10.4 mm) or
M12 connector according to DIN EN 61076-2-101 (optional on request)
Housing
plastic, UV-stabilised,
material polyamide, 30 % glass-globe reinforced,
with quick-locking screws
(slotted/ Phillips head - combination),
colour traffic white (similar to RAL 9016)
Connecting head
made of plastic, material polycarbonate (PC), colour white,
pluggable, Ø = approx. 35 mm, H = approx. 29 mm
Protection type
IP 67