Voltage supply
24 V AC (± 20 %) and
15…36 V DCVoltage supply
24 V AC (± 20 %) and
15…36 V DC
Power consumption
< 1.5 VA/ 24 V DC, < 3.5 VA/ 24 V AC
Load resistance
RL > 5 kOhm
Deviation of humidity
typical ± 2.0 % r. H. (20…80 % r. H. ); at + 25 °C, otherwise ± 3.0 % r. H.
Temperature deviation
typically ± 0.2 K at +25 °C
Ambient temperature
storage –35...+85 °C,
operation – 30...+70 °C, non-precipitating
Electrical connection
0.14 - 1.5 mm² via terminal screws
Housing
plastic, material ABS,
colour pure white (similar to RAL 9010)
Output
potential-free changeover contacts
(2 x changeover contact 24 V, 1A ohmic load, separately adjustable,
1x 0 - 10 V)
Housing dimensions
98 x 98 x 35 mm (Baldur 2)
Sensor
digital humidity sensor
with integrated temperature sensor,
low hysteresis, high long-term stability
Operating difference
Mode 1: both switch steps are freely adjustable (rel. humidity)
Mode 2: 5 % between both switch steps (rel. humidity)
Mode 3: both switch steps freely adjustable (temperature)
Mode 4: switch step 1 (temperature), switch step 2 (rel. humidity)
(adjustable via DiP switches)
Long-term stability
± 1 %/ year
Protection class
III (according to EN 60 730)
Setting range
5...95 % r.H. (Humidity)
+5...+ 45 °C (Temperature)
(switch steps 1 and 2 are separately adjustable)
Protection type
IP 30