Voltage supply
24 V AC (± 20 %) and
15…36 V DC
Power consumption
< 1,0 VA/ 24 V DC
< 2,2 VA/ 24 V AC
Load resistance
RL > 5 kOhm
Measuring range, humidity
0...100 % r. H.
(output corresponding to 0 -10 V)
Operating range, humidity
0...95 % r. H. (without dew formation)
Deviation of humidity
typical ± 2 % r. H. (20…80 % r. H. ); at + 25 °C, otherwise ± 3 %
Output, humidity
0 - 10 V
Measuring range, temperature
0...+ 50 °C
(output corresponding to 0 -10 V or 4... 20 mA or Ohm value)
others upon request!
Operating range, temperature
0...+50 °C
Temperature deviation
typically ± 0.2 K at +25 °C
Output, temperature
0 - 10 V
Ambient temperature
storage –25...+50 °C,
operation –5...+55 °C
Electrical connection
2-, 3- or 4-wire connection
0.14 -1.5 mm ² via terminal screws on circuit board
Housing
plastic, material ABS,
colour pure white (similar to RAL 9010)
Dimensions
85 x 85 x 27 mm (Baldur 1)
Installation
wall mounting or on in-wall flush box, Ø 55 mm,
base with 4 holes, for attachment to vertically or
horizontally installed in-wall flush boxes for rear cable entry,
with predetermined breaking point for cable entry
from top/ bottom in case of plain on-wall installation