DIN relay coupler DRK-1/L

€24.90
Tax included

Switching on lighting fixtures can result in very high inrush currents. A closing contact bounces 3-7 times until it closes completely. This creates an arc that can melt the contact surface. If the closed contact cools down, micro-welding can occur (contact sticks).

To avoid contact sticking, relays with a leading tungsten contact are used.

This allows switch-on peaks of 165 A / max. 20 ms for incandescent lamps, or 800 A / max. 200 µs for fluorescent lamps. 

An 8-pin connection comb is available for quick wiring of the negative pole A2.

1 circuit with 12 A

The circuit can switch a power of 12A / 250 V AC and inrush peaks of 165 A / 20 ms, or 800 A / 200 µs.

DIN 45 mm housing

With its standardized housing, the coupling module can be installed behind the cover with a 45 mm cut-out, taking up a width of only 17.5 mm. The switching status indicators (LEDs) are visible, the AUTO-OFF-ON switches are accessible, and the connections are protected behind the cover.

DRK-1/L

9 same category products: