Voltage supply
24 V AC/ DC (± 10 %)
Load resistance
RL > 50 kOhm
Switch-on start-up time
< 1 min
Response time
t90 < 5 s
Input
1 x 0 -10 V control input DDC
1 x 0 -10 V ascading input
Measuring range
0...+15 °C
Accuracy
typically ± 1 K (at +10 °C)
Process connection
by mounting clamps MK- 05 - K
(included in the scope of delivery)
Electrical connection
0.14 - 1.5 mm² via terminal screws
Output
1 x 0 -10 V output temperature (corresponding to 0...+15 °C)
1 x 0 -10 V output valve
(frost signal with control voltage and cascading)
1 x potential-free changeover contact (24 V),
range of adjustment 0...+15 °C
Housing dimensions
126 x 90 x 50 mm (Tyr 2)
Current consumption
max. 100 mA at 24 V DC
Cable gland
M 16 x 1.5, including strain relief, exchangeable,
max. inner diameter 10.4 mm
Ambient temperatures
Sensor and capillary tube: –20...+60 °C
(capillary tube at a distance of > 20 cm from the housing)
Housing: –15...+50 °C
Storage/ transport: –30...+70 °C
Hysteresis of switching step
2K
Permissible air humidity
< 95 % r. H., non-precipitating air
Housing
plastic, UV-stabilised,
material polyamide, 30 % glass-globe reinforced,
with quick-locking screws
(slotted/ Phillips head - combination),
colour traffic white (similar to RAL 9016),
housing cover for display is transparent !
Protection class
III (according to EN 60 730)
Protection type
IP 65 (according to EN 60 529)*
Sensor and capillary
Copper sensor rod, length of 3 m or 6 m,
active along the entire sensor length,
min. response length of 25 cm
Standards
CE conformity,
electromagnetic compatibility according to EN 61326,
according to EMC Directive 2014/ 30/ EU
Features
display with illumination, three-line, cutout approx. 70 x 40 mm
(W x H), for displaying the actual temperature, measuring
range overrange/underrange of the set switch point (frost
protection temperature), and alarm indicator for "frost" or
"error" (capillary breakage, overvoltage/undervoltage)