Switching capacity (Contact load)
24 … 250 V AC + 10 %, 16 A, cos = 1.0
24 … 250 V AC + 10 %, 1.5 A, cos = 0.6
at 24 V AC min. 150 mA
Contact
dust-proof switch block unit as potential-free
single-pole changeover contact
Process connection
endless metal strap and metal tightener
(included in scope of delivery)
Strap dimensions
Ø = 13 - 92 mm (¼ - 3"), L = 300 mm
Housing dimensions
108 x 70 x 73,5 mm (Thor 2)
Housing temperature
–35...+65 °C
Cable gland
M 20 x 1.5; including strain relief
Design principle
torsion meter with liquid filling
Operating difference
5K (± 1K)
Tolerance
Tmin ± 5 K; Tmax ± 5 K
Protection class
I (according to EN 60 730)
Protection type
IP 65 (according to EN 60 529)*
Standards
CE conformity,
EMC directive 2014/ 30/ EU,
low-voltage directive 2014/ 35/ EU
Housing
plastic, UV-stabilised,
material polyamide, 30 % glass-globe-reinforced,
colour traffic white (similar to RAL 9016)
Function
Heating: The preset setpoint (scale value) is equivalent to the switch-off value of the heating.
The switch-on value is lower by the amount of operating difference.
Contact 2 - 3 breaks when temperature rises to the preset value.
Cooling: The preset setpoint (scale value) is equivalent to the switch-on value of the cooling.
The switch-off value is lower by the amount of operating difference.
Contact 1 - 2 closes when temperature rises to the preset value.