Switching capacity (Contact load)
24…250 V AC +10 %, 10 A, cos = 1.0
24…250 V AC +10 %, 1.5 A, cos = 0.6
at 24 V AC min. 150 mA
Contact
dust-proof switch block unit as potential-free,
single-pole or two-pole changeover contact
Ambient temperature
–10...+65 °C at the switch block housing
Operating medium
Air
Process connection
by mounting flange
(included in the scope of delivery)
Protective tube
metal, material CuZn37 (2.0321),
Ø 14 mm, NL = 205 mm
Inserted length
approx. 205 mm (with flange);
approx. 184 mm (without flange)
Mounting position
arbitrary
Electrical connection
0.14 - 2.5 mm²
via terminal screws
Housing
plastic, UV-stabilised,
material polyamide, 30 % glass-globe-reinforced,
colour traffic white (similar to RAL 9016)
Housing dimensions
108 x 70 x 73,5 mm (Thor 2)
Cable gland
M 20 x 1.5; including strain relief
Tolerance
Tmin ± 5 K; Tmax ± 3 K
Protection class
I (according to EN 60 730)
Protection type
IP 65 (according to EN 60 529)*
Measuring element
torsion meter with liquid filling,
liquid expansion temperature feeler
Standards
CE conformity,
EMC directive 2014/ 30/ EU,
low-voltage directive 2014/ 35/ EU
Tests
EC type test (module B) according to directive 2014/ 68/ EU,
certificate No.: IS -TAF - MUC 18 03 2652130 002, DIN EN 14597,
register Nos.: STB 1201, TR/ STB 1202
Function
TW, TR:
Contact 2 - 3 breaks when temperature rises
to the preset value.
STB:
Contact 2 - 1 or 5 - 4 (two-step) breaks when temperature rises
to the preset value.
Restart is possible only after cooling off by
approx. 15 K - 20 K by pressing the reset button.