Power consumption
< 1,0 VA/ 24 V DC
< 2,2 VA/ 24 V AC
Voltage supply
15...36 V DC
depending on working resistance, residual ripple stabilised ± 0.3 V
Working resistance
Ra (ohm) = (Ub -14 V)/ 0.02 A for I variant
Sensor
Pt1000, DIN EN 60751, class B
Connection type
2- or 3-wire connection
Measuring ranges
multi-range switching
with 8 switchable measuring ranges,
see table (other ranges optional)
Tmin –30 °C, Tmax +80 °C
with manual zero point correction (± 10 K)
Ambient temperature
Measuring transducer –30...+70 °C
Sleeve
stainless steel, 1.4571, V4A
Probe
active along the entire sensor length
Electrical connection
0.14 - 1.5 mm²
via terminal screws on circuit board
Cable connection
cable gland, plastic (M 16 x 1.5; with strain relief, exchangeable, max. inner diameter 10.4 mm) or
M12 connector according to DIN EN 61076-2-101 (optional on request)
Housing dimensions
72 x 64 x 37,8 mm (Tyr 1)
Cable gland
M 16 x 1.5, including strain relief, exchangeable,
max. inner diameter 10.4 mm
Installation
observe minimum bending radius of 35 mm and
permissible vibration load, ½ G
Output
4...20 mA
Permissible air humidity
< 95 % r. H., non-precipitating air
Protection class
III (according to EN 60 730)
Standards
CE conformity,
electromagnetic compatibility according to EN 61326,
according to EMC Directive 2014/ 30/ EU
Process connection
by mounting flange, plastic
(galvanised steel optional, see accessories)
and mounting clamps MK - 05 - M
Rod material
copper sensor tube, plastic-coated,
with spring for buckling protection
Sensor and rod dimensions
Ø = 5.0 mm,
nominal length NL = 3 m
(nominal length optional up to max. 20 m)
Protection type
IP 65