Power consumption
< 1.0 VA/ 24 V AC/ DC; < 0.55 VA/ 24 V DC
Voltage supply
15...36 V DC
depending on working resistance, residual ripple stabilised ± 0.3 V
Working resistance
Ra (ohm) = (Ub -14 V)/ 0.02 A for I variant
Temperature deviation
typically ± 0.2 K at +25 °C
Sensor
Pt1000, DIN EN 60751, class B
(Perfect Sensor Protection)
Connection type
2- or 3-wire connection
Ambient temperature
Measuring transducer –30...+70 °C
Process connection
by means of immersion sleeve or mounting flange
(accessories)
Protective tube
stainless steel, 1.4571, V4A, Ø = 6 mm
Electrical connection
0.2 - 1.5 mm², via push-in terminal
Output
4...20 mA
Permissible air humidity
< 95 % r. H., non-precipitating air
Protection class
III (according to EN 60 730)
Measuring ranges
multi-range switching with 8 switchable measuring ranges,
(other ranges optional)
T = +150°C
with manual zero point correction (± 10 K)
Protection type
IP 54 (according to EN 60 529) standard
IP 65 (according to EN 60 529) optional
Cable connection
adjusting screw made of metal (M 20 x 1,5);
optional with cable gland, brass,
nickel-plated (M 20 x 1,5 ; with strain relief, exchangeable,
inner diameter 6 - 12 mm) or
M12 connector according to DIN EN 61076-2-101 (on request)
Connecting head
form B, material aluminium,
colour white aluminium (similar RAL 9006),
ambient temperature –30...+70° C