Power consumption
< 1,0 VA/ 24 V DC
< 2,2 VA/ 24 V AC
Voltage supply
15...36 V DC
depending on working resistance, residual ripple stabilised ± 0.3 V
Working resistance
Ra (ohm) = (Ub -14 V)/ 0.02 A for I variant
Temperature deviation
typically ± 0.2 K at +25 °C
Sensor
Pt1000, DIN EN 60751, class B
(Perfect Sensor Protection)
Connection type
2-wire connection
Ambient temperature
Measuring transducer –30...+70 °C
Process connection
endless metal strap and metal tightener
(included in scope of delivery)
Insulating resistance
100 MΩ,
at +20 °C (500V DC)
Strap dimensions
Ø = 13 - 92 mm (¼ - 3"), L = 300 mm
Electrical connection
0.14 - 1.5 mm² via terminal screws
Housing dimensions
143 x 97 x 61 mm (Tyr 2E)
Output
4...20 mA
Permissible air humidity
< 95 % r. H., non-precipitating air
Sensor protection
pipe feeder, stainless steel V4A (1.4571), Ø = 6 mm,
nominal length NL = 50 mm, cable entry stamped
Protection class
III (according to EN 60 730)
Protection type housing
IP 65 (according to EN 60 529)
Housing tested, TÜV SÜD, Report No. 713160960B (Skadi2)
Measuring ranges
multi-range switching with 8 switchable measuring ranges,
(other ranges optional)
detached sensor variant: Tmax over 100 °C, operating range –50... +150 °C;
with manual zero point correction (± 10 K)
Cable connection
cable gland, brass, nickel-plated
(M 20 x 1.5; with strain relief, exchangeable,
inner diameter 6 - 12 mm)
Housing
stainless steel V4A (1.4571),
with non-distortion cover bolting,
impact-resistant, high EMI shielding,
corrosion, temperature, UV and weathering resistant
sensor cable
silicone, SiHF, 2 x 0.25 mm², KL = 1.5 m (other lengths and
range limits optional, e.g. PTFE leads up to +250 °C
or glass fibre with steel wire mesh up to +350°C)
Protection type (sensor)
IP 65