Outside temperature / wet room temperature measuring transducer THERMASGARD® ATM2-I

€107.70
Tax included

Calibratable THERMASGARD® ATM 2 outside temperature measuring transducer with eight switchable measuring ranges, external sensor, continuous output, housing made of impact resistant plastic with quick-release screws, optionally with/without display, with cable gland or M12 connector according to DIN EN 61076-2-101.

The transmitter serves to detect outside temperatures, temperatures in wet rooms, and is installed e.g. on outside walls, in cold storage buildings and greenhouses, in the industrial sector and in agriculture. Installation in outdoor areas is preferably performed at the north side of a building or in a protected place.

THERMASGARD®
Protection type
Output model
Output
Display
Quantity

Voltage supply

15...36 V DC

depending on working resistance, residual ripple stabilised ± 0.3 V

Power consumption

< 1,0 VA/ 24 V DC

< 2,2 VA/ 24 V AC

Working resistance

Ra (ohm) = (Ub -14 V)/ 0.02 A for I variant

Temperature deviation

typically ± 0.2 K at +25 °C

Output

4...20 mA

Sensor

Pt1000, DIN EN 60751, class B

(Perfect Sensor Protection)

Connection type

2- or 3-wire connection

Measuring ranges

multi-range switching with 8 switchable measuring ranges,

see table (other ranges optional)

operating range –30...+70 °C

with manual zero point correction (± 10 K)

Ambient temperature

Measuring transducer –30...+70 °C

Process connection

by screws

Protective tube

stainless steel V4A (1.4571), Ø 6 mm, NL = 65 mm

Electrical connection

0.14 - 1.5 mm² via terminal screws

Cable connection

cable gland, plastic (M 16 x 1.5; with strain relief, exchangeable, max. inner diameter 10.4 mm) or

M12 connector according to DIN EN 61076-2-101 (optional on request)

Housing

plastic, UV-stabilised,

material polyamide, 30 % glass-globe reinforced,

with quick-locking screws

(slotted/ Phillips head - combination),

colour traffic white (similar to RAL 9016)

Housing dimensions

72 x 64 x 37,8 mm (Tyr 1)

Cable gland

M 16 x 1.5, including strain relief, exchangeable,

max. inner diameter 10.4 mm

Permissible air humidity

< 95 % r. H., non-precipitating air

Protection class

III (according to EN 60 730)

Protection type

IP 65

1101-1142-0009-900