Voltage supply
15...36 V DC
depending on working resistance, residual ripple stabilised ± 0.3 V
Power consumption
< 1,0 VA/ 24 V DC
< 2,2 VA/ 24 V AC
Working resistance
Ra (ohm) = (Ub -14 V)/ 0.02 A for I variant
Temperature deviation
typically ± 0.2 K at +25 °C
Output
4...20 mA
Sensor
Pt1000, DIN EN 60751, class B
(Perfect Sensor Protection)
Connection type
2- or 3-wire connection
Measuring ranges
multi-range switching with 8 switchable measuring ranges,
see table (other ranges optional)
operating range –30...+70 °C
with manual zero point correction (± 10 K)
Ambient temperature
Measuring transducer –30...+70 °C
Process connection
by screws
Protective tube
stainless steel V4A (1.4571), Ø 6 mm, NL = 65 mm
Electrical connection
0.14 - 1.5 mm² via terminal screws
Cable connection
cable gland, plastic (M 16 x 1.5; with strain relief, exchangeable, max. inner diameter 10.4 mm) or
M12 connector according to DIN EN 61076-2-101 (optional on request)
Housing
plastic, UV-stabilised,
material polyamide, 30 % glass-globe reinforced,
with quick-locking screws
(slotted/ Phillips head - combination),
colour traffic white (similar to RAL 9016),
housing cover for display is transparent !
Housing dimensions
72 x 64 x 43.3 mm (Tyr 1 with Display)
Cable gland
M 16 x 1.5, including strain relief, exchangeable,
max. inner diameter 10.4 mm
Permissible air humidity
< 95 % r. H., non-precipitating air
Protection class
III (according to EN 60 730)
Protection type
IP 65