Voltage supply
24 V AC/ DC (± 10 %) and 15...36 V DC
Power consumption
< 1.5 VA/ 24 V DC, < 2.8 VA/ 24 V AC
Load resistance
RL > 5 kOhm
Output
0 -10 V
1 changeover contact (24 V), 1 A ohmic load
Output signal
0 -10 V
1 changeover contact (24 V), 1 A ohmic load
Connection type
3-wire connection
Measuring function
Volume flow, differential pressure,
filter monitoring, fill level (adjustable)
Measuring ranges
10...100% (adjustable)
Media temperature
–20...+50 °C
Type of pressure
differential pressure
Above- below-pressure
máx. ± 10000 Pa
Medium
clean air and
non-aggressive, non-combustible gases
Signal filtering
switchable 1 s/ 10 s
and small value suppression < 1 %
Signal hysteresis
± 1 % or final value (pressure) 10 Pa/ 50 Pa
Electrical connection
0.14 - 1.5 mm², via plug-in screw terminal
Pressure connection
equipped as standard with quick connect made from stainless steel
for PVC-fabric pressure hose Ø 6 mm ( 4/ 8 mm optional)
optionally with pipe fitting, stainless steel V2A (1.4305)
for pressure lines Ø 6 mm
Housing dimensions
143 x 97 x 61 mm (Tyr 2E)
Sum of Linearity+hysteresis
< ± 1 % of final value
Accuracy
(1000 Pa): typically ± 5 Pa
compared to the calibrated reference device
Temperature drift values
± 0.1 %/ °C
Air humidity
< 95 % r. H., non-precipitating air
Protection class
III (according to EN 60 730)
Cable connection
M12 connector (male, 12-pin, A-code)
according to DIN EN 61076-2-101
K factor
1 to 3000 (adjustable)
Housing
stainless steel V4A (1.4571),
with non-distortion cover bolting,
impact-resistant, high EMI shielding,
corrosion, temperature, UV and weathering resistant