• Analogue manual or emergency operation
The coupling module can switch to manual or
watchdog mode. This allows an analogue signal of
0 - 10 V to be generated independently of a
controller.
• DIN 45 mm housing
The standardised housing enables the coupling
module to be installed by means of a 45 mm cutout behind the covering; it only requires a width of
17.5 mm for this.
Input side
Rated voltage Un A1 - A2 24 V AC/DC
Tolerance -15%; +10%
Power consumption DC 0.4 - 1 W
Watchdog input signal 24 V DC / ca. 25 mA
Output side
Switching voltage Y 0 - 10 V DC
Feedback signal (manual) 24 V DC / ca. 25 mA
General data
Ambient temperature -20°C … +60°C
Storage temperature -30°C … +70°C
Mounting position Any
Fixing DIN rail EN 50022-35
Protection class of front IP 40
Voltage limitation class III
Degree of contamination 2
Connection cross section 2.5 mm2
Weight 86 g
Standards EN 61812-1, EN 50081, EN 61000