• Analogue manual mode
The coupling module can be switched over to manual mode. This allows an analogue signal of 0 - 10 V
or 0 - 20 mA to be generated independently of a
controller.
• AUTO-OFF-ON with feedback
The coupling mode can switch to automatic or
manual mode. In automatic mode the contact with
feedback is closed, therefore a logic 1 results on the
controller. Multiple feedbacks can be connected in
series.
• DIN 45 mm housing
The standardised housing enables the coupling
module to be installed by means of a 45 mm cutout
behind the covering, it only requires a width of 17.5
mm for this.
Imput side
Rated voltage Un A1 - A2 24 V AC/DC
Tolerance -15%; +10%
Current consumption at 24 V AC / 24 V DC 27 mA / 24 mA
Input signal YR 0 - 10 V / 0 - 20 mA
Output side
Output signal Y 0 - 10 V DC / 0 - 20 mA
Output current in manual switch position 1 mA (at 10V)
Output status indicator Green LED (brightness proportional to the output signal)
Switch for feedback
Max. switching capacity 100 mA / 30 V
General data
Relative turn-on-time 100%
Switching AUTO / MAN Short-circuit-proof
Ambient temperature -20°C … +55°C
Storage temperature -30°C … +70°C
Mounting position Any
Fixing DIN rail EN 50022-35
Protection class of front IP 40
Voltage limitation class III
Degree of contamination 2
Connection cross section 2.5 mm2
Weight 52 g
Standards EN 61000-6-3, EN 60730-1