Supply and measuring terminals A1 - A2
Supply and measuring voltage 6 … 30 V DC
Power consumption DC max. 1.2 VA
Setting and accuracy
Over range (Umax.) 18 … 30 V DC
Under range (Umin.) 35 … 95 % von Umax.
Time delay 0 … 10 sec adjustable
Setting accuracy (mechanically) 5 %
Output side
Number of contacts 1 changeover contact
Switching voltage 250 V AC1 / 24 V DC
Switching current / contact material 16 A / AC1 / AgNi
Max. peak current 30 A / < 3 s
Switching capacity 4000 VA / AC1, 384 W / DC
Min. switching capacity DC 500 mW
Output display red / green LED
General data
Mechanical life 3 x 107
Electrical life 0.7 x 105
Ambient temperature -20°C … +60°C
Storage temperature -30°C … +70°C
Test voltage coil / contact 2.5 kV
Mounting position Any
Fixing DIN rail EN 50022-35
Protection class of front IP 40
Voltage limitation class III
Degree of contamination 2
Connection cross section 2.5 mm2
Weight 60 g
Standards EN 61812-1, EN 50081, EN 61000
Repetitive accuracy < 1 %
Temperature dependence < 0.1 % / K
Limit tolerance 5 %
Hysteresis 2 … 6 % of the set value
Max continuous operating voltage 36 V DC
peak voltage 50 V DC, < 1 ms